First open the drain valve to drain the nitrogen, and then close the drain valve.

Rated 5/5 based on 570 customer reviews
Share:
Content

First open the drain valve to drain the nitrogen, and then close the drain valve. Open the exhaust valve and introduce the LNG gas in the LNG tank box into the LNG tank through the unloading platform. When the pressure in the tank rises to 0.1-0.2MPa, close the exhaust valve, stabilize for 3 minutes, and open the drain valve to empty. Repeat this 2-3 times until the replacement is complete. A combustible gas detector or exhaust gas sampling can be used for ignition test to check the degree of replacement.